Product Categories

Insertion Type Electromagnetic Btu Meter

MODEL: FLOWMAG1600H

FLOWMAG1600H Insertion electromagnetic BTU / heat meter (or magnetic BTU meters) measures the thermal energy consumption in heating and cooling applications where hot-tap or insertion installations are preferred, It is comprised of a converter, a flow sensor and 2 temperature sensors. Then flow sensor is inserted through the hole on the pipeline, and the converter picks up the voltage signals generated by the fluid passing the electrodes of the sensor, and the 2 temperature sensors are installed on the inlet pipe and outlet pipe separately, the converter picks up the signals sensors, and calculate the heat according to the flow volume and the temperature difference between the inlet and outlet pipelines. then convert the voltage to the readings on the integrated LCD display or a control system.,
FLOWMAG1600H can be used for measuring thermal energy consumption in heating or cooling application for HVAC and other thermal energy measurement and metering installations in large diameter pipes .

Contact us

Email

info@cbroindia.com sales@cbroindia.com

Sales Support

+917021306718

Technical Support

+918591988100

Advantages

For precise measurement of the heat or cold energy in a water heating/cooling circuit, this Insertion Type Electromagnetic Btu Meter is used. It is made up of the main unit, two temperature sensors, and an electromagnetic flow sensor. The powerful console that combines highly accurate flow measurement, temperature measurement, and BTU calculation makes up the primary unit. This information is used to compute the thermal power and energy needed to maintain the temperature at the specified level.

Applications

  • Chilled Water HVAC
  • Hot Water HVAC
  • Condensate And Heating Water Circuits
  • Boiler Feed Water
  • Thermal Storage, Geothermal System, Solar Hot-water System
  • District Energy Management And Billing
  • Commercial Building Tenant Billing
  • Leed / Green Building Verification,Green Credit Application
  • Energy Consulting
  • Power Plant Efficiency Monitoring
  • Facility Management In Shopping Malls, Campus, Industial Parks, Hospitals, Commercial Buildings,
  • Government Buildings, Airports And More

Water Treatment

Food Industry

Pharmaceutical Industry

Petrochemical

Paper Industry

Chemical Monitoring

Metallurgical Industry

Public Drainage

Coal Industry

Technical Specifications

Table 1: Insertion Type Electromagnetic Btu Meter/ Heat Meter

Transmitter
Make
CBRO
Moodel
FLOWMAG1600H
Medium
Hot Water, Chilled water
Diameter
DN50~DN3000mm
Accuracy
±1% of read
Temp. range
-20~+150℃
Pressure
1.6 MPa
Temperature Sensors
PT100 2nos Inlet / Outlet
Straight pipe
Upstream ≥5DN,Downstream ≥3DN
Electrode
316L,Hastelloy C(HC),Titanium(Ti),Tantalum(Ta),Platinum(Pt)
Lining
ABS / PTFE
Installation way
Without a ball valve or with a ball valve
Body material
Stainless steel
Display
16*4 line LCD DIsplay with 3 Control Buttons
Display Options
Flow /Velocity / Temp / Energy
Measuring Units
Flow : m3/h Energy : MJ/h ; GJ/h ; KWh/h ; MWh/h
Display Mounting
Integrated / Remote Digital Display
Electric Entry
M20*1.5
Power supply
220VAC/24VDC/Lithium battery
Signal output
Pulse output,4~20mA
Communication
RS485,Hart, GPRS, BACnet etc.
Explosion proof
Optional
Protection class
IP65(compact type), IP68(remote type)
Working environment
Temp. Range: -20~+60℃,humidity: 5%~90%
Data Back-up
Auto save data when the power is off
Power Failure
Have back up battery for data saving